45
CHAPTER 3 SPECIFICATIONS
3
3.1 Performance Specifications
*1 A Universal model QCPU can be set to a station No. within the range of No.1 to No.120.
For a module other than Universal model QCPUs, station No.1 to No.64 can be set.
*2 A station with a Basic model QCPU or safety CPU operates as a normal station. (It cannot be set to a control station.)
*3 All I/O signals of the CC-Link IE Controller Network module are used by the system. (Use prohibited)
*4 Two I/O slots are occupied.
In the Start I/O No. field of Network parameter, set a value obtained by adding 10
H
to the I/O No. of the module-installed
slot. Note that 0 point can be set instead of 16 points for the first half in I/O assignment of PLC parameter.
Laser class (IEC 60825-1) Class 1 laser product
Number of occupied I/O points
32 (Intelli.: 32 points)
*3
48 (I/O assignment: Empty first half: 16 points,
Latter half: 32 points for intelli.)
*3*4
External
power
supply
Voltage
No external power supply function
20.4V to 31.2V DC
Current 0.28A
Terminal screw size M3
Applicable solderless
terminal
R1.25-3
Applicable wire size
0.3 to 1.25mm
2
Tightening torque 0.42 to 0.58N•m
Allowable
momentary power
failure time
1ms (Level PS1)
Noise immunity
By noise simulator of 500Vp-p noise voltage, 1µs
noise width, and 25 to 60Hz noise frequency
Internal current consumption (5V
DC)
0.85A 0.90A
External dimensions 98 (H) × 27.4 (W) × 90 (D) [mm] 98 (H) × 55.2 (W) × 90 (D) [mm]
Weight 0.18kg 0.28kg
When the module is installed to slot 0, set 10
H
to the start I/O number.
(When setting 0 points for the slot 0 by I/O assignment setting, set 0
H
for the start I/O number.)
Item
Specification
QJ71GP21-SX QJ71GP21S-SX