518
E204
H
Transient data resend count
exceeded
The specified number of
resends has been reached.
• Check the network status in the CC IE Control
diagnostics.
• Check the program to see if the time of resends has
been set when executing the instruction.
E205
H
Receive buffer full The receive buffer is full.
• Temporarily stop the transient transmission, and then
retry it.
• Reduce the operation frequency of transient
transmission and retry the operation.
• Using the COM instruction, increase the processing
frequency of transient transmission.
( Page 326, Section 9.2.1)
• If the error persists even after taking the above actions,
please consult your local Mitsubishi representative.
E206
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E207
H
Transient data receiving
network No. error
Although the data are sent
and received within the same
network, network numbers of
the own and target stations
are different.
• Check the network numbers of the own and target
stations in Network parameters, and execute it again.
E208
H
Transient data target station
No. error
The target station No. setting
is not correct.
• Confirm the target station No. on the own station, and
retry the operation.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E209
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E20A
H
E20B
H
Transient data relay count
error
The number of relay stations
exceeded the upper limit.
• Modify the system configuration so that the number of
relay stations is seven or less.
• Check if the routing parameters are set correctly.
• To perform the IP communication test, check the IP
address of the destination. Then set the number of relay
stations within 127.
E20C
H
to
E20E
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E20F
H
Transient data target station
No. error
The target station No. is zero
(0).
• Confirm the target station No. on the own station, and
retry the operation.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E210
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E211
H
Invalid assign control station
No. in transient data
The specified "assign control
station" does not exist.
• Confirm the target station No. on the own station, and
retry the operation.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E212
H
Invalid present control station
No. in transient data
The specified "present control
station" does not exist.
E213
H
Transient data transmission
completion wait time timed
out
Timeout has occurred without
transmission completion.
• Check the network status in the CC IE Control
diagnostics.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E214
H
to
E21A
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
Error code Error Error detail Corrective action