520
E257
H
Resend count specification
error (Dedicated instruction)
The number of resends was
not set correctly.
• Confirm the number of resends in the control data, and
retry the operation.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E258
H
Target network No. error
(Dedicated instruction)
The target network No. was
not set correctly.
• Confirm the target network No. in the control station,
and retry the operation.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E259
H
Target station channel error
(SEND instruction)
Target station channel is not
set correctly for the SEND
instruction.
• Check the Target station channel in the control data,
and then retry the instruction.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E25A
H
Modification specification
error (UINI instruction)
Modification specification is
not set correctly for the UINI
instruction.
• Check the Modification specification in the control data,
and then retry the instruction.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E25B
H
Own station No. error (UINI
instruction)
Incorrect own station No. is
set for the UINI instruction.
• Check the own station No. set in the control data, and
then retry the instruction.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E25C
H
to
E261
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E262
H
Arrival confirmation error
(Dedicated instruction)
In all stations or group
designation, the dedicated
instruction was executed
"with arrival confirmation" set
for the execution type.
For the REQ instruction, the
set request type is not
correct.
• Change the execution type in the control data to "No
arrival confirmation", and retry the operation.
• For the REQ instruction, check the request type in the
request data, and retry it.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E263
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E264
H
Transmission completion wait
time timeout error (Dedicated
instruction)
Timeout has occurred without
transmission completion.
• Check the network status in the CC IE Control
diagnostics.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E265
H
Response timer timeout error
(Dedicated instruction)
Timeout has occurred without
response reception.
• Check the network status in the CC IE Control
diagnostics.
• Check the version of the CC-Link IE Controller Network
compatible device on the target station.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
A CC-Link dedicated
instruction was executed to a
station that does not support
CC-Link dedicated
instructions.
E266
H
Unsupported request
reception error (Dedicated
instruction)
The SEND instruction was
received from any other
station.
• Change the target station at the station where the
SEND instruction was executed.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E267
H
Target station No. error
(Dedicated instruction)
The own station No. was set
as the target station No.
• Confirm the target station No. in the control data, and
retry the operation.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
Error code Error Error detail Corrective action