574
SB0053
Cyclic transmission
stop completion status
(system)
Turned ON when Cyclic transmission stop accept status (system)(SB0052) is
turned ON and cyclic transmission stop is completed.
OFF: Stop uncompleted (SB0003 is OFF)
ON: Stop completed (SB0003 is ON)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
SB0054
Parameter receive
status
Stores the status of receiving parameters.
The parameter receive status from the CPU module is stored for the control
station.
The parameter receive status from the control station is stored for the normal
station.
OFF: Receive completed
ON: Receive uncompleted
SB0055
Received parameter
error
Stores the status of received parameter (Own parameter status is stored for
the control station)
OFF: Parameter normal
ON: Parameter error
SB0056 Communication status
Stores the transient transmission status.
OFF: Transient transmission by control station
ON: Transient transmission by sub-control station
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
SB005A Parameter type
Stores Network Type of the control station.
OFF: CC IE Control
ON: CC IE Control Extended Mode
SB005B
Own station's CPU
RUN status
Stores the RUN status of the CPU module of the own station.
OFF: RUN, STEP-RUN
ON: The CPU module stop due to STOP, PAUSE, or error
SB005C
I/O master station
(Block 1)
Stores the I/O master station setting status of block 1.
OFF: No setting
ON: Setting set
When the setting is set, the station No. is stored into I/O master station (Block
1) (SW005C).
(Condition)
• Valid when Data link status of own station (SB0049) is OFF.
SB005D
I/O master station
(Block 2)
Stores the I/O master station setting status of block 2.
OFF: No setting
ON: Setting set
When the setting is set, the station No. is stored into I/O master station (Block
2) (SW005D).
(Condition)
• Valid when Data link status of own station (SB0049) is OFF.
SB005E
Own station's CPU
type
Stores the CPU type of the own station.
OFF: Other than Basic model QCPU and safety CPU
ON: Basic model QCPU or safety CPU
No. Name Description
Availability
Control
station
Normal
station