EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q Series - Page 602

Mitsubishi Electric MELSEC-Q Series
674 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
600
SW0150
to
SW0157
OUT-side error frame
reception detection
status
Stores whether the error frame is received or not in the OUT-side transmission
path of each station from power-on to the present.
The stored value is cleared when Clear OUT-side transmission error counter
(SB0008) is turned ON.
0: A line error has not yet occurred on the transmission path of each
station's OUT.
1: A line error occurred on the transmission path of each station's OUT.
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only for the normally operating station at Baton pass status of each
station (SW00A0 to SW00A7).
SW0160
to
SW0167
Path switching
detection status of
each station
Stores whether the path switching is detected or not in each station from
power-on to the present.
The path switching detection status is cleared when Clear loop switching
counter (SB0009) is turned ON.
Turn ON Clear loop switching counter (SB0009) when clearing the path
switching detection status of other station.
0: Path switching not detected
1: Path switching detected
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
No. Name Description
Availability
Control
station
Normal
station
SW0151
SW0152
SW0153
SW0154
SW0155
SW0156
SW0157
SW0150 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
b15
b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
--------120119118117116115114113
Each number in the table represents station No.
SW0161
SW0162
SW0163
SW0164
SW0165
SW0166
SW0167
SW0160 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
b15
b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
--------120119118117116115114113
Each number in the table represents station No.

Table of Contents