EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q Series - Page 606

Mitsubishi Electric MELSEC-Q Series
674 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
604
SW01D0
to
SW01D7
Redundant system
status (1)
Stores the CPU operation mode of each station (including the own station).
0: Backup mode (including single systems)
1: Separate mode
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
• Valid only for the normally operating station at Baton pass status of each
station (SW00A0 to SW00A7).
• The reserved station and the station No. later than the largest one are
excepted.
SW01E0
to
SW01E7
Redundant system
status (2)
Stores the pairing setting status of each station (including the own station).
0: No pairing setting (including single systems)
1: Pairing setting
If pairing is set, the bit corresponding to the system B station is ON.
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
• Valid only for the normally operating station at Baton pass status of each
station (SW00A0 to SW00A7).
• The station No. later than the largest one are excepted.
No. Name Description
Availability
Control
station
Normal
station
SW01D1
SW01D2
SW01D3
SW01D4
SW01D5
SW01D6
SW01D7
SW01D0 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
Each number in the table represents station No.
--------
SW01E1
SW01E2
SW01E3
SW01E4
SW01E5
SW01E6
SW01E7
SW01E0 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
Each number in the table represents station No.
--------

Table of Contents

Other manuals for Mitsubishi Electric MELSEC-Q Series

Related product manuals