618
(e) Comparison of other functions
: compatible, : partially changed, —: incompatible
Function Compatibility Precautions for replacement
Interrupt request to CPU module
The CC-Link IE Controller Network module
does not have an interrupt of scan completion.
Replace with other interrupt condition.
Multiplex transmission function
The CC-Link IE Controller Network module
does not have this function.
The high-speed communication can be
realized without multiplex transmission
function in the CC-Link IE Controller Network
module since link scan time of the CC-Link IE
Controller Network is shorter than that of the
MELSECNET/H module.
Increase of send points by mounting multiple network modules of the
same network No.
Check the software version.
( Page 606, Appendix 3)
Debug mode —
The CC-Link IE Controller Network module
does not have this function.
Simplified duplexing of network —
Redundant system
• For the CC-Link IE Controller Network
module, the system switching monitoring
time is set with a network parameter.
Since it has been set with SB0018/SW0018
for the MELSECNET/H, delete the relevant
part of the existing sequence program.
• When the CC-Link IE Controller Network
module is used, link output (LY) data cannot
be sent from the standby system station.
• The circuit test or station-to-station test must
be executed in separate mode for the CC-
Link IE Controller Network module.