A station with a Basic model QCPU or safety CPU will receive another station's data in LB/LW0 to 3FFF, which is set in
"LB/LW Setting(2)", however, they will not be refreshed to the CPU module's devices.
Only the direct access to link devices is available. ( Page 70, Section 4.1.4)
(b) When a station other than Universal model QCPUs exists on the network
The station cannot receive other stations' data of station No.65 and higher.
(c) When a Universal model QCPU exists on the network
If the group cyclic transmission function is used, the station can receive other stations' data of the same shared
group and those of the stations to which no shared group is set.
It does not receive data of other stations in different shared groups. ( Page 83, Section 4.1.8)
Universal model
QCPU
Universal model
QCPU
Universal model
QCPU
Basic model QCPU
Control station (No.1) Normal station (No.2) Normal station (No.3) Normal station (No.4)
Link register (LW)
No.1 send range
No.1 send range
No.2
No.3
No.4
No.2
No.4
No.1
No.1
No.2 send range
No.3
No.4
No.2 send range
No.4
No.1
No.1
No.2
No.3 send range
No.4
No.2
No.4
No.1
No.1
No.2
No.3
No.4 send range
No.2
No.4 send range
LW0
LW4000
Not refreshed to CPU module devices.
Accessible only by direct access to link
devices.
Setting range of
LB/LW settings (1)
Setting range of
LB/LW settings (2)
Control station
No.1
Normal station
No.64
Normal station
No.120
No.1 send range
No.64
No.120
LB/LW
No.1
No.64
No.120 send range
Universal model QCPU High Performance model QCPU Universal model QCPU
No.1
No.64 send range