8 Settings via the MICT
Rev. 03/2019 125
Status message Description
Output board identification failed
due to unknown error number.
The identification of the output board failed due to
unknown error number. Characteristic data of the output
board could not be read, they are defective or do not
match the device. Restart the ignition controller. If the
error occurs again after restarting the device, please
contact MOTORTECH.
Output board identification failed
due to unknown hardware.
The identification of the output board failed due to
unknown hardware. Characteristic data of the output
board could not be read, they are defective or do not
match the device. Restart the ignition controller. If the
error occurs again after restarting the device, please
contact MOTORTECH.
Pickup configuration invalid. The pickup configuration is invalid. This message may
appear during an upgrade/downgrade. Check your
configuration data and the MICT version being used. Then
download the configuration to the device once again.
Power failure detected on output
Anumber/Bnumber.
Power supply fault in output board at output
Anumber/Bnumber was detected. Restart the ignition
controller. If the error occurs again after restarting the
device, please contact MOTORTECH.
Power output (x W) exceeded error
threshold limit (y W) at a supply
voltage of z V.
The power output (x W) exceeded failure threshold (
y
W) at
a supply voltage of z V. Increase the supply voltage and
check the energy settings (see Timing – Schedule A/B –
Energy on page 104).
Power output (x W) exceeded limit
(y W) at a supply voltage of z V.
The power output (x W) exceeded warning threshold limit
(y W) for longer than two minutes at a supply voltage of
z V . Increase the supply voltage and check the energy
settings (see Timing – Schedule A/B – Energy on
page 104).
The power output (x W) exceeded
permanent limit (y W) at a supply
voltage of z V.
The power output (x W) exceeded warning threshold limit
(y W) for longer than three minutes at a supply voltage of
z V . Increase the supply voltage and check the energy
settings (see Timing – Schedule A/B – Energy on
page 104).
PUnumber: Faulty index. The pickup PUnumber has an error in index. Check the
pickups and the corresponding configuration (see Engine
– Pickups on page 96). Furthermore, also pay attention to
the instructions in the section entitled Pickup Input Errors
on page 164.