9 Messages
Maschinenfabrik Reinhausen 2014 1313550953/00 EN TAPCON® 230 pro
Messages
No. Event (yel-
low/red)
Event message Remark
3 Red Undervoltage Message is displayed in the event of undervoltage.
Set the Undervoltage U< [ 78] parameter.
4 Red Overvoltage Message is displayed in the event of overvoltage.
Set the Overvoltage U> [ 80] parameter.
5 Red Overcurrent Message is displayed in the event of overcurrent.
Set the Overcurrent I> [ 82] parameter.
6 Red Parallel operation error: Dif-
ferent parallel operation
methods
Message is displayed if different parallel operation
methods are set for 2 or more devices in the same
parallel operation group. Set the Parallel operation
method parameter.
7 Yellow Motor protection device Triggered by the motor protective switch input.
9 Yellow Undercurrent Message is displayed in the event of undercurrent.
Set the Undercurrent I< [ 83] parameter.
11 Red Error when setting user in-
puts (duplicate assignment)
At least 2 user inputs are parameterized to the
same function. Message is displayed after the 2nd
parameter has been confirmed with .
12 Yellow Function monitoring (voltage
not adjusted within set time)
Message is displayed if the voltage has not been
adjusted within the set time (presetting: 15 mi-
nutes).
13 Yellow Motor-drive unit runtime
monitoring
Message is displayed if the set motor runtime is ex-
ceeded. Setting motor runtime monitoring [ 65]
parameters.
14 Red Analog input value too high.
Check your connection to
terminal X7!
Message is displayed when the maximum permissi-
ble current of 20 mA is exceeded for connection
X7.
15 Yellow Negative analog input value
Check your connection to
terminal X7!
Message is displayed in the event of reverse polari-
ty or if X7 connection is incorrectly connected.
16 Red Parameter reloaded! Confirm
with F3 & Enter
Message is displayed if the current set of parame-
ters is corrupt or damaged and the system has
therefore switched to the standard set of parame-
ters.
17 Yellow Check sliding contact. Message is displayed if the resistor contact series
is incorrectly connected or has a loose contact.
18 Yellow No other CAN bus partici-
pants present
Message is displayed if parallel operation has been
set but there is not a device in the same parallel op-
eration group or the CAN bus is actually interrupt-
ed.
19 Red Parallel operation error: Cir-
culating reactive current
blocking limit exceeded
Message is displayed if the parallel operation meth-
od is using circulating reactive current or master/
follower and the blocking limit is activated. The cir-
culating reactive current limit must also be exceed-
ed.