7 Functions and settings
Maschinenfabrik Reinhausen 2014 1093550953/00 EN TAPCON® 230 pro
Setting upper limit value of input signal [%]
To configure the analog input, you must state the upper limit value for the in-
put signal. Use the following settings depending on your analog signal:
Analog signal Setting
Injected current: 0/4...20 mA 100 % (= 20 mA)
Resistor contact series always 100 %
Table 25: Parameter settings
To assign the maximum tap position to the analog value, proceed as follows:
1. > Configuration > Continue > Continue > Tap
position > Press until the desired parameter is displayed.
ð Analog Val. [%] Tap pos. max.
2. Press to highlight a digit.
ð The desired position is highlighted and the value can be changed.
3. Press to increase the value or to reduce it.
4. Press .
ð The analog value for the maximum tap position is assigned.
Setting upper value of input signal
To configure the analog input, an absolute value must be assigned to the up-
per value of the applied signal.
To set the highest tap position, proceed as follows:
1. > Configuration > Continue > Continue > Tap
position > Press until the desired parameter is displayed.
ð Highest tap position
2. Press to increase the value or to reduce it.
3. Press .
ð The highest tap position is set.
Setting the desired voltage level remotely
The analog input can also be used to change the desired voltage value re-
motely. This requires the analog input (terminal strip X7) to be adapted to
the voltage level transmitter signal.
The analog input (terminal strip X7) can be used either for the input of the
tap position or for setting the desired voltage level remotely.