EasyManua.ls Logo

MR tapcon 230 pro - Page 95

MR tapcon 230 pro
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Functions and settings
Maschinenfabrik Reinhausen 2014 953550953/00 EN TAPCON® 230 pro
Setting Measurement meth-
od
Phase difference
-30 3PH 3 phase -30°
Table 18: Set values for transformer circuit
Note the following sample circuits to select the correct transformer circuit.
Circuit A: 1-phase measurement in 1-phase grid
TAPCON® 230
Figure 54: Phase difference 0 1PH
The voltage transformer VT is connected to the outer conductor and
neutral conductor.
The current transformer CT is looped into the outer conductor.
The voltage V
L1
and current I
L1
are in phase.
The voltage drop on an outer conductor is determined by the current I
L1
.
Circuit B: 1-phase measurement in 3-phase grid
TAPCON® 230
Figure 55: Phase difference 0 3PHN
The voltage transformer VT is connected to the outer conductors L1 and
the neutral conductor.
The current transformer CT is looped into the outer conductor L1.
The voltage V and current I are in phase.
The voltage drop on an outer conductor is determined by the current I
L1
.

Table of Contents

Related product manuals