12 Overview of parameters
Maschinenfabrik Reinhausen 2014156 222/08 ENTAPCON® 240
Parameter Setting range Factory setting Current setting
Configuration > Parallel operation
Blocking 0.5...20 % 20.0 %
CAN address 0...16 1
Error message 1...99 s 10 s
ParErrorIfAlone On/Off Off
Parallel operation method Off, circulating reactive
current; master; follow-
er; synch. auto
Off
SKB parallel operation On/Off Off
Stability 0...100 % 0.0 %
Tapping direction Swapped Standard/Swapped Standard
Configuration > Analog inputs
Input 1 upper limit 0...100 % 100.0 %
Input 1 lower limit 0...100 % 0.0 %
Input 1 upper value -999.9...999.9 0.0
Input 1 lower value -999.9...999.9 0.0
Input 2 upper limit 0...100 % 0.0 %
Input 2 lower limit 0...100 % 0.0 %
Input 2 upper value -999.9...999.9 0.0
Input 2 lower value -999.9...999.9 0.0
Configuration > LED selection
LED1 See [ 112] Off
LED2 See [ 112] Off
LED3 yellow See [ 112] Off
LED4 green See [ 112] Off
LED4 red See [ 112] Off
Configuration > Measuring transducer 1/2
Output 1 measured value See [ 114] Off
Output 1 upper value -9999...9999 0
Output 1 lower value -9999...9999 0
Output 1 upper 1 mA; 10 mA; 20 mA;
N/A
20 mA
Output 1 lower See [ 114] +4 mA
Output 2 measured value See [ 114] Off
Output 2 upper value -9999...9999 0
Output 2 lower value -9999...9999 0
Output 2 upper 1 mA; 10 mA; 20 mA;
N/A
20 mA
Output 2 lower See [ 114] +4 mA
Configuration > Measuring transducer 3/4
Output 3 measured value See [ 114] Off