EasyManua.ls Logo

MR tapcon 240 - Page 75

MR tapcon 240
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Functions and settings
Maschinenfabrik Reinhausen 2014 75222/08 EN TAPCON® 240
If one of the requirements listed below is not met, the active-power-depend-
ent desired value adjustment is not activated. Desired value 1, desired val-
ue 2 or desired value 3 is automatically used for regulation depending on
the setting.
You must set the following parameters with valid values:
Power-dependent desired value must be set to ON
Maximum active-power-dependent desired value
Minimum active-power-dependent desired value
Desired value at active power = 0
Active power at maximum desired value
Active power at minimum desired value
A valid active power is measured
A current transformer must be connected to measure the current
A valid voltage is measured
Depending on device configuration, there are 3 ways in which the active-
power-dependent desired value adjustment can be activated/deactivated:
On the device using the control panel
REMOTELY using a control input on the IO card, UC1 card or UC2 card
REMOTELY using SCADA
Activating/deactivating parameters on device
To activate or deactivate the power-dependent desired value adjustment,
proceed as follows:
1. > Parameter > Control parameter > Press until the
desired parameter is displayed.
ð Power-dependent desired value.
2. Press or to select the option you want.
3. Press .
ð The power-dependent desired value adjustment is activated/deactivat-
ed.
Activating/deactivating parameters via a control input
Depending on configuration, you can also activate the active-power-depend-
ent desired value adjustment via an input on the following cards:
IO card
UC1 card
UC2 card

Table of Contents

Other manuals for MR tapcon 240

Related product manuals