7 Functions and settings
Maschinenfabrik Reinhausen 201474 222/08 ENTAPCON® 240
Response to value falling below active power P
min
If the measured active power P
meas
falls below the set parameter P
min
, the val-
ue U
min
is adopted as the desired value.
Response to a measured active power P
meas
= 0 MW:
If the measured active power P
meas
= 0, the set parameter U
0
is adopted.
Linear dependency with negative active power:
If the measured active power P
min
≤ P
meas
≤ 0, the desired value is calculated
using the following formula:
Linear dependency with positive active power:
If the measured active power 0 ≤ P
meas
≤ P
max
, the desired value is calculated
using the following formula:
To activate the active power-dependent desired value adjustment, set all the
parameters described in the following sections.
Activating/deactivating power-dependent desired value adjustment
You can use this parameter to activate or deactivate the active-power-de-
pendent desired value adjustment. When you activate the active-power-de-
pendent desired value adjustment, all the following requirements must be
met for this function to be active:
7.4.6.1