Figure 25 shows a typical SCADA PCM multidrop bridge network.
Figure 25 SCADA PCM Multidrop Bridge Network
The PCM multidrop bridge application uses Mu-Law and A-Law encoding; therefore, 
the modularity is different from MDDB modularity. Table 22 shows the modularity for 
a PCM multidrop bridge on the Integrated Services card.
Table 22 PCM Multidrop Bridge Modularity
Encoding Scheme Number of 
Bridges per 
Integrated 
Services Card
Number of 
Branches per 
Bridge
Total Number 
of Branches 
per Integrated 
Services Card
Mu-Law (North America) 16 22 352
A-Law (rest of world) 16 30 480
SCADA IED 1
Remote 1
SCADA IED 2
Remote 2
SCADA IED 255
Remote n
SCADA
SERVER 1
Control Center A
SCADA
SERVER 2
Control Center B
7705 SAR
7705 SAR 7705 SAR7705 SAR
MPLS
Network
25433
E&M
Legend: