The name option lets users assign a more meaningful name (must be unique) to the
alarm input; for example, windowOpen3 might be more meaningful to a user than the
identifier alarm-1/3.d-3. Once the name has been configured, it can be used
interchangeably with the alarm input identifier; for example, windowOpen3 can be
used instead of alarm-1/3.d-3 as an alarm input trigger.
input
Syntax input alarm-input
Context config>external-alarms
Description This command enables the context to configure the external alarm inputs on 7705 SAR
Ethernet ports, on the Auxiliary Alarm card, and on the four alarm inputs on the fan module
(for the 7705 SAR-8), alarm connector (for the 7705 SAR-M (all variants), 7705 SAR-H,
7705 SAR-Hc, and 7705 SAR-X), and alarm module (for the 7705 SAR-18).
An alarm input must be associated with an alarm in order for the input to be triggered. See
the trigger command. An input can be associated with up to four alarms.
Default n/a
Parameters alarm-input — identifies the alarm input
for Ethernet ports, the format is:
port-slot/mda/port [name]
for the Auxiliary Alarm card, the format is:
alarm-slot/mda.{d | a}-alarm-num [name]
for the four alarm inputs on the fan module (for the 7705 SAR-8), alarm connector
(for the 7705 SAR-M (all variants), 7705 SAR-H, 7705 SAR-Hc, and 7705 SAR-X),
and alarm module (for the 7705 SAR-18), the format is:
alarm.d-alarm-num [name]
where:
slot = card slot number for IOM (always 1 on the 7705 SAR)
mda = Ethernet adapter card or Auxiliary Alarm card slot number (for Ethernet
modules or ports on platforms with no card slots, the mda slot number is
preconfigured)
port = port number for Ethernet ports
d = digital input
a = analog input
alarm-num = alarm port number (1 to 24 for digital on the Auxiliary Alarm card, 1
to 4 for digital on the four chassis alarm inputs, 1 or 2 for analog)
name = optional name assigned to the input
for example: