Interface Configuration Guide 7705 SAR Interfaces
Edition: 01 3HE 11011 AAAC TQZZA 335
alarm-1/3.d-3
windowOpen3
alarm.d-1
The name option lets users assign a more meaningful name (must be unique) to the
alarm input; for example, windowOpen3 might be more meaningful to a user than the
identifier alarm-1/3.d-3. Once the name has been configured, it can be used
interchangeably with the alarm input identifier; for example, windowOpen3 can be
used instead of alarm-1/3.d-3 as an alarm input trigger for the trigger command, or
when performing a show>external-alarms>input or show>external-alarms>
output command.
debounce
Syntax debounce seconds
debounce detect detect-seconds clear clear-seconds
no debounce
Context config>external-alarms>input
Description This command configures the debounce time associated with detecting and clearing an alarm
input. Debounce time is not supported on alarm inputs on Ethernet ports.
The no debounce form of the command sets both the detect time and clear time to 0.
Default 2 (for both detect time and clear time)
Parameters seconds — specifies the amount of time that the input must be on or off before it is
accepted as changed from on to off (or from off to on)
Values 1 to 60
detect-seconds — specifies the amount of time that the input must be on before it is
accepted as on by the system
Values 0 to 60
clear-seconds — specifies the amount of time that the input must be off before it is
accepted as off by the system
Values 0 to 60
output
Syntax output alarm-output
Context config>external-alarms
Description This command enables the context to configure the external alarm output relays.
Default n/a