Interface Configuration Guide 7705 SAR Interfaces
Edition: 01 3HE 11011 AAAC TQZZA 521
squelch
Syntax squelch timeout timeout
squelch reset
no squelch
Context config>scada>mddb
config>scada>pcm
Description This command enables the squelching function for all branches configured on a bridge. This
setting takes priority over the setting at the branch level; that is, if squelch is disabled with this
command, it cannot be enabled for individual branches.
The no form of this command disables the squelching function on a bridge.
Default no squelch
Parameters timeout — the interval between when an alarm is raised indicating that a branch has
locked up and is continuing to send data to the master, and squelching is triggered
Values 1 to 120 s
reset — puts the bridge back into the normal state
squelch-recovery
Syntax squelch-recovery [mode] [time time]
Context config>scada>mddb
config>scada>pcm
Description This command configures squelch recovery attributes. When the squelch-recovery mode is
configured as auto, the branch will automatically be put back into the normal state after the
configured time. If the branch remains locked up, the branch will automatically be squelched
again.
Configuring the squelch-recovery mode as manual disables automatic squelch recovery. To
put the bridge back into the normal state, use the squelch reset command.
Default squelch-recovery manual
Parameters mode — specifies the squelch recovery mode
Values manual | auto
time — the interval after which the branch will automatically be put back into the normal
state
Values 1 to 120 s