C004
4.1 Overcurrent measurement
"Overcurrent measurement"
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
• FI is overloaded
• Drive sluggish, insufficiently sized
• Ramps (P102/P103) too steep -> Increase ramp time
• Check motor data (P201 … P209)
• Switch off slip compensation (P212)
Pos: 679 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 008 [SK 180 E ... SK 5xxE] @ 2\ mod_1347457201563_388.docx @ 47249 @ @ 1
C008
8.0 Parameter loss
Warning:
One of the cyclically saved messages such
as operating hours or enabling time
saved successfully.
The warning disappears as soon as saving can be
successfully performed.
Pos: 68 0 /Anlei tung en/El ektr onik/FU und St art er/6 . M eld ung en z um B etr iebs zus ta nd/S tör mel dung en (Auf list ung )/ Warn ung C 01 2 [S K 180 E ... SK 2xxE ] @ 2\mod_1347457201968_388.docx @ 47274 @ @ 1
C012
12.1 Limit moto./Customer
"Drive switch-off limit"
Warning: 80 % of the drive switch-off limit (P534 [-01]) has
been exceeded.
• Reduce load on motor
• Set higher value in (P534 [-01]).
12.2 Limit gen.
"Generator switch-off limit"
Warning: 80 % of the generator switch-off limit (P534 [-02])
has been reached.
• Reduce load on motor
• Set higher value in (P534 [-02]).
12.3 Torque limit
Warning: 80 % of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
12.4 Current limit
Warning: 80 % of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
12.5 Load monitor
Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
• Adjust load.
• Change limit values ((P525) ... (P527)).
• Increase delay time (P528).