14-90
Num-
ber
Name Boolean Operand Description Steps
F149
P149
Message
display
MSG
PMSG
S Displays the character constant of “S” in the
connected programming tool.
13
F150
P150
Data read
from intelli-
gent unit
READ
PREAD
S1, S2, n,
D
Reads the data from the intelligent unit. 9
F151
P151
Data write
into intelli-
gent unit
WRT
PWRT
S1, S2, n,
D
Writes the data into the intelligent unit. 9
F152
P152
Data read
from
MEWNET-F
slave station
RMRD
PRMRD
S1, S2, n,
D
Reads the data from the intelligent unit at the
MEWNET-F (remote I/O) slave station.
9
F153
P153
Data write
into
MEWNET-F
slave station
RMWT
PRMWT
S1, S2, n,
D
Writes the data into the intelligent unit at the
MEWNET-F (remote I/O) slave station.
9
F154
P154
Machine
language
program call
MCAL
PMCAL
n The machine language program is called. 3
F155
P155
Sampling SMPL
PSMPL
- Starts sampling data. 1
F156
P156
Sampling
trigger
STRG
PSTRG
- When the trigger of this instruction turns on, the
sampling trace stops.
1
F157
P157
Time addition CADD
PCADD
S1, S2, D The time after (S2+1, S2) elapses from the time of
(S1+2, S1+1, S1) is stored in (D+2, D+1, D).
9
F158
P158
Time
substruction
CSUB
PCSUB
S1, S2, D The time that results from subtracting (S2+1, S2)
from the time (S1+2, S1+1, S1) is stored in (D+2,
D+1, D).
9
F159
P159
Serial port
communica-
tion
MTRN
PMTRN
S, n, D This is used to send data to an external device
through the specified CPU COM port or MCU COM
port.
7
F161
P161
MCU serial
port
reception
MRCV
PMRCV
S, D1, D2 Data is received from external equipment via the
COM port of the specified MCU.
7