SLINK Control Unit FP0
4 10
4.5 Operation When Power Supply is Turned On
4.5 Operation When Power Supply is Turned On
Refreshing SLINK I/O data
With the SLINK control unit, I/O data is refreshed by the CPUs of both the FP0 section
and the SLINK section, through the memory shared between them.
Shared
memory
I/O data refreshed
I/O data
area
refreshed
SLINK control unit
SLINK
section
CPU
FP0
section
CPU
The illustration below shows the time required until the first refreshing is completed by
the SLINK control unit after the power supply has been turned on. (The external power
supply for the SLINK is already on.)
2.6 seconds
SLINK section
I/O data
refreshed
0.07 seconds
FP0 section
I/O data area
refreshed
Power supply of SLINK
control unit turned on
When the power supply to the SLINK control unit is turned on, it takes approximately
2.6 seconds for the SLINK I/O data to be verified by the FP0 section. Be particularly
careful with regard to the FP0 sequence program, if using the SLINK input at the b
contact relay when the power supply is turned on.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP0 and is the answer not in the manual?

Panasonic FP0 Specifications

General IconGeneral
ModelFP0
Communication PortsRS232C, RS485
Power Supply24V DC
Operating Temperature0°C to 55°C
TypeProgrammable Logic Controller (PLC)
I/O Points16 to 128

Related product manuals