EasyManua.ls Logo

Parker ac890 - Chapter 4 890 CS & 890 CD Common Bus Units

Parker ac890
640 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
890CS & 890CD Common Bus Units
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page
4-3
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
8
9
1
2
3
4
5
6
E
Main Points
These are modular, cubicle-mounted units. They are not suitable for wall-mounting.
Mount the Modules side-by-side vertically on a solid, flat, normally cool, non-flammable, vertical
surface.
The 890CS Common Bus Supply is normally mounted to the left of the 890CD Common Bus Drive(s).
The units can be DIN rail or panel mounted.
Fit the 890 Installation kit to the bottom of the drive.
Adequate ventilation must be provided.
Avoid excessive vibration.
The earth points (D, E, G, M & S) are shown separated - it may be possible to use one large star point
without EMC problems, this will depend upon your application.
Note Refer to Appendix C for information about EMC compliance.
Sizing the Enclosure
The enclosure must comply with the European safety standards VDE 0160 (1994)/EN50178 (1998) and
will require a tool for opening.
The size of the enclosure will depend on many factors:
Physical size and number of units
Ventilation clearances
Power output, affected by derating due to altitude and ambient temperature
Figure 4.1 A Typical Layout of a Cubicle (wiring not shown)

Table of Contents

Other manuals for Parker ac890

Related product manuals