EasyManua.ls Logo

Parker ac890 - DIGITAL OUTPUT

Parker ac890
640 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page
D-23
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
DIGITAL OUTPUT
SETUP::INPUTS & OUTPUTS::DIGITAL OUTPUT
The digital output block converts a logic TRUE or FALSE demand to a physical output signal.
Parameter Descriptions
VALUE
PREF: 17.01, 18.01, 19.01 Default: FALSE Range: FALSE / TRUE
The TRUE or FALSE output demand.
Functional Description
There is a DIGITAL OUTPUT function block associated with each of the following terminals:
The Control Board has 2 configurable digital inputs/outputs. These share terminals X15/08 and X15/09. Also refer to
CUSTOM TRIPS, page D-20.
DOUT1 is associated with terminal X15/08
DOUT2 is associated with terminal X15/09
The default status for these 2 DOUTs is to act as inputs. Setting VALUE to TRUE will individually configure the block to be
an output.
The Control Board has one digital output (volt-free relay contacts):
DIGITAL OUTPUT 3 is associated with the "HEALTH" outputs, DOUT3A & DOUT3B. These are terminals X14/01
and X14/02 respectively.
VALUE
OUTPUT

Table of Contents

Other manuals for Parker ac890

Related product manuals