Programming
Page
D-76
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
MOT POLARISATION
SETUP::MOTOR CONTROL::MOT POLARISATION
Designed for PMAC control mode
This function is used to set up and verify the relative position between the position sensor and the PMAC motor.
Parameter Descriptions
SWITCH ON START
PREF: 156.01 Default: MANUAL Range: MANUAL
Selects the method of starting the pole finding sequence. This parameter is automatically set to MANUAL (where the pole
finding sequence is initiated by the POLAR START parameter).
POLARISATION
PREF: 156.02 Default: DISABLE Range: DISABLE / ENABLE
Set this parameter to ENABLE to enter the resolver calibration mode.
POLAR START
PREF: 156.03 Default: FALSE Range: FALSE / TRUE
Set this parameter to TRUE to start the calibration process (state only available if POLARISATION = ENABLE).
TYPE
PREF: 156.04 Default: 1:STANDARD Range: 1:STANDARD
Selects the type of pole finding method. This parameter is automatically set to STANDARD.
Enumerated Value : Type
0 : 1:STANDARD Method used by 99% of applications (motor must be free to rotate).
1:MOTOR PHASE
PREF: 156.05 Default: U PHASE Range: See below
Selects the position to polarise the motor when the TYPE parameter is set to STANDARD.
Enumerated Value : Motor Phase
0 : U PHASE = 90°
1 : V PHASE = -150° (or 210° )

Table of Contents

Other manuals for Parker ac890

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker ac890 and is the answer not in the manual?

Parker ac890 Specifications

General IconGeneral
BrandParker
Modelac890
CategoryDC Drives
LanguageEnglish

Related product manuals