EasyManua.ls Logo

Parker ac890 - Page 279

Parker ac890
640 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Keypad Menus
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page 9-23
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
QUICK SETUP MENU
890CD Common Bus Drive & 890SD Standalone Drive
PREF 6511/6901
Display
Description Range Default
70.01
QUADRATIC
TORQUE
TIME (s)
150%
% OF RATED MOTOR CURRENT
30 60
100% overload for 30s (Heavy Duty)
127.5%
105%
100%
FALSE - CONSTANT: Inverse time allows
150% overload for 60s, then ramps back the
current limit to 105% over a 10s period. At a
lower load, the overload area remains the
same, e.g. at 127.5% load for 120s - after
120s has expired, the output of the inverse
time function is ramped back over a 10s
period from 150% as before.
TRUE - QUADRATIC: current limit is set to
110% motor current, inverse time delay is set
to 30s
0=FALSE
1=TRUE
Note that 890 Frames
B, C & D have no
quadratic torque current
rating.
0
70.13
MOTOR CURRENT
This parameter contains the motor nameplate
full-load line current
0.01 to 999.99A product
code
dependent

Table of Contents

Other manuals for Parker ac890

Related product manuals