Keypad Menus
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page 9-25
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
QUICK SETUP MENU
890CD Common Bus Drive & 890SD Standalone Drive
PREF 6511/6901
Display
Description Range Default
27.03
(induction
motor
only)
MOTOR BASE
FREQ
The output frequency at which maximum
voltage is reached. The default is Product
Code dependent
7.5 to 1000.0 Hz 50.0 Hz
27.04
(induction
motor
only)
* MOTOR
VOLTAGE
This parameter contains the motor nameplate
voltage at base frequency
0.0 to 575.0V product
code
dependent
27.07
(induction
motor
only)
* NAMEPLATE RPM
This parameter contains the motor nameplate
full-load rated speed. This is the motor speed
in rpm at base frequency minus full load slip
0.0 to 30000.0 RPM product
code
dependent
27.09
(induction
motor
only)
MOTOR POLES
This parameter contains the number of motor
poles, as supplied on the motor nameplate
0=2 pole
1=4 pole
2=6 pole
3=8 pole
4=10 pole
5=12 pole
1
27.08
(induction
motor
only)
* MOTOR
CONNECTION
This parameter contains the motor nameplate
connection.
0= DELTA
1= STAR
1