Keypad Menus
Page 9-28 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
QUICK SETUP MENU
890CD Common Bus Drive & 890SD Standalone Drive
PREF 6511/6901
Display
Description Range Default
78.01
SPEED PROP GAIN
Sets the proportional gain of the loop.
Speed error (mechanical rev/s) x proportional
gain = torque percent.
0.0 to 3000.0 product
code
dependent
78.02
SPEED INT TIME
This is the integral time constant of the speed
loop. A speed error which causes the
proportional term to produce a torque
demand T, will cause the integral term to also
ramp up to a torque demand T after a time
equal to “speed int time”.
1 to 15000ms product
code
dependent
1.03
AIN 1 TYPE
Selects input range for Analog Input 1. 0 = -10..+10 V
1 = 0..+10 V
0
2.03
AIN 2 TYPE
Selects input range for Analog Input 2. 0 = -10..+10 V
1 = 0..+10 V
0
3.03
AIN 3 TYPE
Selects input range for Analog Input 3. 0 = -10..+10 V
1 = 0..+10 V
2 = 0..20 mA
3 = 4..20 mA
0
4.03
AIN 4 TYPE
Selects input range for Analog Input 4. 0 = -10..+10 V
1 = 0..+10 V
2 = 0..20 mA
3 = 4..20 mA
0