Loading...
Trips and Fault Finding
8
9
10
11
A
B
C
D
1
2
3
4
5
6
6511
Keypad
Display
6901
Keypad
Display
Description Possible Reason for Trip
I HI CURRENT LIMIT V/Hz mode only: If the
current exceeds 180% of
induction stack rated
current for a period of 1
second, the drive will trip.
This is caused by shock
loads
Remove the cause of the shock load
A24SC 24V FAILURE The 24V customer output
has fallen below 17V
24V customer output is short circuited
Excessive loading
LSPD LOW SPEED OVER I The motor is drawing too
much current (>100%) at
zero output frequency
FIXED BOOST and/or AUTO BOOST set too high
(refer to FLUXING menu at level 3)
PHAS PHASE FAIL
One or more input phases not present
ENC 1 FBK ENCODER FAIL
Encoder fault
SHRT DESAT (OVER I)
Instantaneous overcurrent. Refer to
OVERCURRENT in this table
7
E
Page
10-8
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D

Table of Contents

Other manuals for Parker ac890