EasyManua.ls Logo

Parker ac890 - Page 417

Parker ac890
640 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page
D-67
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
Parameter Descriptions
TIMEOUT
PREF: 29.07 Default: 600.0 s Range: 0.0 to 600.0 s
Determines the maximum amount of time the sequence is allowed to remain in the low frequency injection braking state.
BASE VOLTS
PREF: 29.08 Default: 100.00 % Range: 0.00 to 115.47 %
Determines the maximum volts at base speed applied to the motor during injection braking.
ACTIVE
PREF: 29.09 Default: FALSE Range: FALSE / TRUE
Indicates the state of the Drive. TRUE when injection braking.

Table of Contents

Other manuals for Parker ac890

Related product manuals