Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page
D-73
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
Parameter Descriptions
POWER UP MODE
PREF: 94.03 Default: 1 Range: See below
Allows the power-up operating mode of the Drive to be selected. Local is the Keypad, Remote is an external signal, Automatic
is the same mode as at power-down. The modes supported are:
Enumerated Value : Power Up Mode
0 : LOCAL
1 : REMOTE
2 : AUTOMATIC
SEQ DIRECTION
PREF: 94.04 Default: FALSE Range: FALSE / TRUE
When TRUE, direction is a Sequencing command.
When FALSE, direction is a Reference command.
REMOTE SEQ
PREF: 94.05 Default: TRUE Range: FALSE / TRUE
This parameter indicates the present source of the sequencing commands.
REMOTE REF
PREF: 94.06 Default: TRUE Range: FALSE / TRUE
This parameter indicates the present source of the reference signal.