EasyManua.ls Logo

Parker ac890 - Page 50

Parker ac890
640 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
890CS & 890CD Common Bus Units
Page
4-30
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
USER 24V DC INPUTS
Name Range Description
01
24V INPUT 24V DC User +24V (2A per unit)
02
24V INPUT 24V DC User +24V (2A per unit)
03
0V INPUT 0V 0V (24V) input
X13
04
0V INPUT 0V 0V (24V) input
Note These connections are not necessary for normal operation of the drive.
Connection can be made from the X01 terminal on the 890CS Common Bus Supply unit. This 24V DC
control supply allows for configuration and commissioning of the system without the DC supply being
present. The drive will operate with this supply but will not turn a motor.
Connection is not required when the DC supply is present, but the connection can be safely left connected.
You can connect an 890CS unit to a maximum of three 890CD units when daisy-chaining 24V using these
terminals (8A maximum). If you have more than three 890CDs, use a 24V rail and wire as shown in the
Wiring Diagram on page 4-
12.