EasyManua.ls Logo

Pulsar ULTRA TWIN - Page 65

Pulsar ULTRA TWIN
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 57
Parameter
Default
Description
P830
mA Out Range
2= 4 to 20 mA
Determines the mA output
range.
0 = Off, 1 = 0 to 20mA,
2 = 4 to 20mA, 3 = 20 to
0mA, 4 = 20 to 4mA.
P870
Fill Damping
32.8084 feet/min
Rate of maximum fill rate (set
above the actual fill rate of the
vessel).
P871
Empty Damping
32.8084 feet/min
Rate of maximum empty rate
(set above the actual empty
rate of the vessel).
The default values used for determining the relay setpoints, when setting
Alarm and Pump relays, via the Quick Setup menu are entered as a % of
span and are as follows.
Application
Number of
Pumps
Pump
Number
On
Setpoint
Off
Setpoint
Pump Down
One
Pump 1
50%
20%
Pump Down
Two
Pump 1
Pump 2
50%
70%
20%
20%
Pump Down
Three
Pump 1
Pump 2
Pump 3
50%
60%
70%
20%
20%
20%
Pump Down
Four
Pump 1
Pump 2
Pump 3
Pump 4
40%
50%
60%
70%
20%
20%
20%
20%
Pump Down
Five
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
40%
50%
60%
70%
75%
20%
20%
20%
20%
20%
Pump Down
Six
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
40%
50%
60%
70%
75%
80%
20%
20%
20%
20%
20%
20%

Table of Contents

Other manuals for Pulsar ULTRA TWIN

Related product manuals