EasyManuals Logo

Qirod QD100 Series User Manual

Default Icon
163 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #107 background imageLoading...
Page #107 background image
105
e-12
DC bus
undervolta
ge fault
Input voltage
is too low.
Adopt
forward/reverse speed
tracking and restart
function (STR function)
(f500 = 1)
Set f418= 2.
e-21
Inverter
overload
Acceleration
time is too short.
DC braking
current level is
too high.
V/f parameter
is wrongly set.
When the
inverter starts,
the load is still in
rotation.
The load is too
large.
Increase acceleration
parameter (f007 or
f617).
Reduce the setting of
f606 and f607.
Correctly set V/f
parameter.
Set parameter f501 =
2.
Use an inverter with
higher rated power.
e-22
Motor
overload
V/f parameter
is wrongly set.
The motor is
blocked.
The motor
continues to run
at low speed.
The load
applied to the
motor is too
large.
Correctly set V/f
parameter.
Check the load.
Code of
fault
Type of fault
Possible cause
Measures
(troubleshooting)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Qirod QD100 Series and is the answer not in the manual?

Qirod QD100 Series Specifications

General IconGeneral
BrandQirod
ModelQD100 Series
CategoryDC Drives
LanguageEnglish