5.19. SETTING THE INTERFACE FUNCTION (INTF Group)
The IMUX 2000 INTF group allows the user to select the interface characteristics as follows: system
type, configure the CM4 for the selected I/O module, and select transmit line buildout.
The IMUX 2000 INTF group functions are summarized in Table 5-11. Refer to Section 7 of this
manual for details on the remote access and control features available.
Table 5-12. INTF group
Subgroup
Or Function
Setting Descriptio
n
TYPE E1 Selects E1 format
T1 Selects T1 format
exit When exit is displayed, press up on the SET/NEXT switch to exit the TYPE subgroup
and display the HEAD fu
nction. To exit the SIO group entirely, press up or down on the
GROUP switch.
HEAD CMI Selects optical interface adapters which support CMI encoding (Code Mark Inversion)
75* Selects 75 ohm termination in E1 mode.
120* Selects 120 ohm termination in E1 mode.
exit When exit is displayed, press up on the SET/NEXT switch to exit the HEAD subgroup
and display the TLBO func
tion. To exit the SIO group entirely, press up or down on the
GROUP switch.
TLBO 0x00 75 ohm normal
0x01 120 ohm normal
0x02 Not used in E1
0x03 Not used in E1
0x04 75 ohm with high return loss
0x05 120 ohm with high return loss
0x06 Not used in E1
0x07 Not used in E1
IMUX 2000E1 RFL Electronics Inc.
exit When exit is displayed, press up on the SET/NEXT switch to exit the TLBO s
ubgroup
and display the TYPE func
tion. To exit the INTF group entirely, press up or down on the
GROUP switch.
5.19.1 SELECTING THE INTF GROUP
To select the INTF group, press up or down on the GROUP switch one or more times until "INTF"
appears in the display. At this point each time the SET/NEXT switch is pressed down, the next INTF
function will be displayed. The three functions in the INTF group are:
1. Type
2. Head
3. TLBO
Each of these three functions each has an additional menu layer beneath them containing more
functions, and may be thought of as subgroups within the INTF function group.