Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
The configuration (setup) of a CM4 Common Module in a redundant multiplexer can be determined by
issuing a CONFIG2? command of the general form:
<Address>:<Subaddress>:<CONFIG2?>:;
For example, to determine the current setup of the DI-A module in a redundant drop/insert multiplexer
with an address of 7, issue the follow command:
7:DI-A:CONFIG2?:;
A typical T1 response might be:
*OK
FROM NET ADDRESS=7
FRAMER=E1
MAIN=ON
SWITCH=AUTO
CSU=RFL
PRSQ=DISA
POSQ=DISA
SWAP=0.6s
UNIT=CM4R
(MODE SWITCH=AUTO)
HEAD=100;
IMUX 2000E1 RFL Electronics Inc.