<M> Settings / Disinfected tank
Maximum range of level sensor [m]
Here you enter the height of the water level (in metres) at
which the maximum sensor level is measured in the
disinfected tank.
Level m
3
= Minimum volume +
(((Level percentage/100) * Maximum range of level
sensor) Height of minimum level) *
((Maximum volume Minimum volume)/
(Height of maximum level - Height of minimum level))
h
100%
Level fixed at 50%
If no level sensor is present, then the measured level can
be set at a fixed level of 50%. This setting is useful, for
example, if a rainwater reservoir is used.
Only set to Yes
if no level
sensor is
present.
8.11 UV lamps
<M> Settings / UV lamp
Replaced
When a UV lamp is replaced, switch this setting to Yes. The lamp on-
time and the number of times that the UV lamp has been activated
(number of starts) will be set to the commissioning values. This setting
will then revert to No automatically.
Lamp on-time when commissioned [h]
Here you enter the value that will be used when the 'Replaced' setting
is switched to Yes.
Numb. starts when commissioned
Here you enter the value that will be used when the 'Replaced' setting
is switched to Yes.
Out of operation
l Yes: The ballast and lamp have been set to out of operation. No
alarms will be generated.
l No: The ballast and lamp are in operation.
Ballast node ID
Here you enter the unique node ID of the ballast. If the value 0 is set
here, then the Node ID number will match the lamp number.