8.9.2 Filter flushing / Safeguards
<M> Settings / Filter flushing / Safeguards
Minimum m3 for start flushing [m3]
This sets the amount of water (in cubic metres) that must pass
through the filter in order for filter flushing to start. If the amount of
water is lower than the value set here, then the alarm message
'Quantity disinfected too low' will be generated and the unit will be
paused.
If a manual start is performed, then the unit will not check whether
this minimum amount of water has passed through the quartz tubes.
Minimum flow [l/min]
If the flow rate drops below the value set here, then the alarm
message 'Flow too low' will be generated. The unit will also be paused.
To disable minimum flow monitoring, set this value to 0.
Minimum flow [l/min]
If the flow rate rises above the value set here, then the alarm
message 'Flow too high' will be generated. The unit will also be
paused.
8.9.3 Filter flushing / Control characteristics
<M> Settings / Filter flushing / Control characteristics
Pump selection filter flushing
Here you select which pump should be used to flush the filter:
l System pump: The main pump of the system.
l Filter flushing pump: A separate filter flushing pump.
Number of sand filters
Here you enter the number of sand filters that are present.
These filters will be flushed consecutively.
8.10 Water tank settings
If more than one water tank is present, you will need to check the data of each tank
individually.