EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-749M - Port Settings (SET P Command); Table 4.41 Front-Panel Serial Port F Settings; Table 4.42 Rear-Panel Serial Port 3 Settings; Table 4.43 Rear-Panel Serial Port 4 Settings

Schweitzer Engineering Laboratories SEL-749M
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.41
Date Code 20080918 Instruction Manual SEL-749M Relay
Protection and Logic Functions
Port Settings (SET P Command)
Port Settings (SET P Command)
The SEL-749M provides settings that allow you to configure the parameters
for the communications ports. See Section 7: Communications for a detailed
description. The front-panel Serial Port F and the rear Port 3 consist of
EIA-232. The rear Port 4 consists of EIA-485 (Port 4A) or EIA-232 (Port 4C).
See Figure 2.3 for the rear-panel layout. Table 4.41 through Table 4.43 show
the serial port settings.
Port F
Port 3
Port 4
Table 4.41 Front-Panel Serial Port F Settings
Setting Prompt Setting Range Setting Name := Factory Default
SPEED 300–38400 bps SPEED := 9600
DATA BITS 7, 8 bits BITS := 8
PARITY O, E, N PARITY := N
STOP BITS 1, 2 bits STOP := 1
PORT TIME-OUT 0–30 min T_OUT := 5
SEND AUTOMESSAGE Y, N AUTO := N
HDWR HANDSHAKING Y, N RTSCTS := N
Table 4.42 Rear-Panel Serial Port 3 Settings
Setting Prompt Setting Range Setting Name := Factory Default
PROTOCOL SEL, MOD PROTO := SEL
SPEED 300–38400 bps SPEED := 9600
DATA BITS 7, 8 bits BITS := 8
PARITY O, E, N PARITY := N
STOP BITS 1, 2 bits STOP := 1
PORT TIMEOUT 0–30 min T_OUT := 5
SEND AUTOMESSAGE Y, N AUTO := N
HDWR HANDSHAKING Y, N RTSCTS := N
FAST OP MESSAGES Y, N FASTOP := N
MODBUS
a
SLAVE ID
a
The Modbus protocol is available at either Port 3 or Port 4, but not both.
1–248 SLAVEID := 1
Table 4.43 Rear-Panel Serial Port 4 Settings
Setting Prompt Setting Range Setting Name := Factory Default
COMM INTERFACE 232, 485 COMMINF := 485
PROTOCOL SEL, MOD PROTO := MOD
SPEED 300–38400 bps SPEED := 19200
DATA BITS 7, 8 bits BITS := 8
PARITY O, E, N PARITY := N
STOP BITS 1, 2 bits STOP := 2
PORT TIMEOUT 0–30 min T_OUT := 0
SEND AUTOMESSAGE Y, N AUTO := N
HDWR HANDSHAKING Y, N RTSCTS := N
FAST OP MESSAGES Y, N FASTOP := N
MODBUS
a
SLAVE ID
a
The Modbus protocol is available at either Port 3 or Port 4, but not both.
1–248 SLAVEID := 248
Courtesy of NationalSwitchgear.com