EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-749M - Figure 10.2 Three-Phase Wye AC Connections; Figure 10.3 Three-Phase Open-Delta AC Connections

Schweitzer Engineering Laboratories SEL-749M
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.5
Date Code 20080918 Instruction Manual SEL-749M Relay
Testing and Troubleshooting
Commissioning Tests
Step 16. Verify that the relay is measuring the magnitude and phase
angle correctly.
The expected magnitude is (applied phase current) (CTRN).
The expected phase angle is zero (0).
Figure 10.2 Three-Phase Wye AC Connections
Figure 10.3 Three-Phase Open-Delta AC Connections
Step 17. Verify control input connections. Using the front-panel
MAIN > TARGETS > ROW 9 function, check the control input
status in the relay.
As you apply rated voltage to each input, the position in Row 9
corresponding to that input should change from zero (0) to one
(1).
Step 18. Verify output contact operation:
a. For each output contact, set the input to Logic 1. This
causes the output contact to close. For example, setting
OUT101 := 1 causes the output OUT101 contact to close.
b. Repeat the process for all contact outputs.
V
C
+120˚
–120˚
PHROT := ACB
V
B
V
A
+120˚
–120˚
V
C
V
B
V
A
PHROT := ABC
When setting PHROT := ABC, set angle V
a
= angle I
a
= 0˚
set angle V
b
= angle I
b
= –120˚
set angle V
c
= angle I
c
= 12
set angle V
a
= angle I
a
= 0˚
set angle V
b
= angle I
b
= 12
set angle V
c
= angle I
c
= –120˚
When setting PHROT := ACB,
60˚
V
AB
V
CB
PHROT := ABC
60˚
V
AB
V
CB
PHROT := ACB
When setting PHROT := ABC,set angle I
a
= 0˚
set angle I
b
= –120˚
set angle I
c
= 12
set angle V
ab
= +3
set angle V
cb
= +90˚
set angle I
a
= 0˚
set angle I
b
= 12
set angle I
c
= –120˚
set angle V
ab
= –3
set angle V
cb
= –90˚
When setting PHROT := ACB,
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals