Table 92: Statuses indicated by the MS LED on the FX3-ANA0 analog input module
MS LED Meaning Notes
o
Supply voltage out of range Switch on the voltage supply of the Flexi Soft sys‐
t
em and check at the A1 and A2 terminals of the
main module.
Ö R
ed/
green (1Hz)
Remediable external error Check cabling of the flashing inputs
Ö Gr
een
(1Hz)
System in Stop status The application can be started using the configu‐
r
ation software.
O Gr
een
System in Run status
Ö R
ed
(1Hz)
Invalid configuration
Ö R
ed
(2Hz)
Serious error in the system,
pr
obably in this module. The
application was stopped. All
outputs are switched off.
Switch thevoltage supply off and then on again.
If the problem still has not been remedied after
multiple repetitions, replace this module.
Use the configuration software diagnostic func‐
tion.
O R
ed
Serious error in the system,
pr
obably in a different mod‐
ule. The application was stop‐
ped. All outputs are switched
off.
Switch thevoltage supply off and then on again.
If the problem still has not been remedied after
multiple repetitions, replace the module showing
Ö red (2Hz). If applicable, also use the diag‐
nostic function in the configuration software to
isolate the affected module.
Table 93: Statuses indicated by the input LEDs on the FX3-ANA0 analog input module
Input LEDs AI1, AI2 Meaning
o
Input is deactivated.
O Green
Input is active.
Ö Gr
een (1Hz) synchronized with the Ö
red/green MS LED (1Hz)
Input is deactivated and there is a remediable
er
ror.
8.7 Status messages of the FX3-MOCx motion control module
For information on the position of the LEDs on the FX3-MOCx motion control module,
see
figure 35, page 59.
8 O
PERATION
112
O P E R A T I N G I N S T R U C T I O N S | Flexi Soft Modular Safety Controller 8012478/1IG6/2023-02-24 | SICK
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Soft and is the answer not in the manual?

SICK Flexi Soft Specifications

General IconGeneral
Safety Integrity Level (SIL)SIL3
Performance Level (PL)PL e
ProgrammingFlexi Soft Designer
Power Supply24 V DC
Safety ProtocolsPROFIsafe, CIP Safety
Protection ClassIP20
Number of I/OsConfigurable
Operating Voltage24 V DC
Power ConsumptionDepends on configuration
Dimensions (W x H x D)Varies depending on the module configuration
WeightVaries depending on the module configuration
Number of Safety InputsConfigurable
Number of Safety OutputsConfigurable
Safety StandardIEC 61508, IEC 62061, ISO 13849
Operating Temperature0°C to +55°C
Response Time< 10 ms (typical)
Storage Temperature Range-25°C to +70°C
Relative Humidity15 % ... 95 %, non-condensing