Figure 46: Example of integrating a relay module into the Flexi Soft system
WARNING
L
imited safety without external device monitoring
The target safety-related level may not be achieved in the event of non-compliance.
Monitor the feedback contacts using an EDM (external device monitoring) function
block in the Flexi Soft logic editor.
5.3 Wiring for the power supply to a Flexi Soft system
Figure 47: Wiring for the power supply to a Flexi Soft system
1
24 V DC
2
System plug
3
Logic
4
FLEXBUS+
5 ELECTRICAL INSTALLATION
76
O P E R A T I N G I N S T R U C T I O N S | Flexi Soft Modular Safety Controller 8012478/1IG6/2023-02-24 | SICK
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Soft and is the answer not in the manual?

SICK Flexi Soft Specifications

General IconGeneral
Safety Integrity Level (SIL)SIL3
Performance Level (PL)PL e
ProgrammingFlexi Soft Designer
Power Supply24 V DC
Safety ProtocolsPROFIsafe, CIP Safety
Protection ClassIP20
Number of I/OsConfigurable
Operating Voltage24 V DC
Power ConsumptionDepends on configuration
Dimensions (W x H x D)Varies depending on the module configuration
WeightVaries depending on the module configuration
Number of Safety InputsConfigurable
Number of Safety OutputsConfigurable
Safety StandardIEC 61508, IEC 62061, ISO 13849
Operating Temperature0°C to +55°C
Response Time< 10 ms (typical)
Storage Temperature Range-25°C to +70°C
Relative Humidity15 % ... 95 %, non-condensing