3.4.6.1 Internal circuitry
Figure 8: Internal structure of the FX3-XTIO – safety inputs and test outputs
1
Internal logic
Figure 9: Internal structure of the FX3-XTIO – safety outputs
1
Internal logic
3.4.6.2 Deactivation of test signals at outputs Q1 to Q4 on the FX3-XTIO
With the FX3-XTIO Step ≥2.xx (firmware versions V2.00.0), it is possible to deactivate
t
he test pulses at one or more outputs of FX3-XTIO modules.
Deactivating the test pulses at one or more of the outputs (Q1 to Q4) of an FX3-XTIO
module reduces the safety parameters of all the outputs (Q1 to Q4) of the module
concerned. If the test pulses are deactivated, a short-circuit cannot be recognized after
24V if the output is high. Therefore, in the case of a recognized internal hardware error,
the switch-off capability of the other outputs can be impaired by the reverse current of
24V via the output whose test pulse has been deactivated. This must be taken into
account to ensure that the application is in line with an appropriate risk analysis and
risk avoidance strategy.
3 P
RODUCT DESCRIPTION
26
O P E R A T I N G I N S T R U C T I O N S | Flexi Soft Modular Safety Controller 8012478/1IG6/2023-02-24 | SICK
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Soft and is the answer not in the manual?

SICK Flexi Soft Specifications

General IconGeneral
Safety Integrity Level (SIL)SIL3
Performance Level (PL)PL e
ProgrammingFlexi Soft Designer
Power Supply24 V DC
Safety ProtocolsPROFIsafe, CIP Safety
Protection ClassIP20
Number of I/OsConfigurable
Operating Voltage24 V DC
Power ConsumptionDepends on configuration
Dimensions (W x H x D)Varies depending on the module configuration
WeightVaries depending on the module configuration
Number of Safety InputsConfigurable
Number of Safety OutputsConfigurable
Safety StandardIEC 61508, IEC 62061, ISO 13849
Operating Temperature0°C to +55°C
Response Time< 10 ms (typical)
Storage Temperature Range-25°C to +70°C
Relative Humidity15 % ... 95 %, non-condensing