The con󹪝guration described gives the following code for the standard module: 0xC1 0x15
0x15 0x00
Diagnostics
Extensive diagnostic possibilities are supported in the PROFIBUS DP. A DP master can query the
current diagnostics from the DP slave at any time. Diagnostic telegrams can write additional
device-speci󹪝c diagnostics in the GSD 󹪝le next to the standard diagnostics.
The DP slave can report in the data telegram at any time that current diagnostics are queued. To
do this it labels its data telegram (High Priority) in the cyclic data communication.
In normal cyclic data communication, the DP slave always answers with a (Low Priority) data
telegram. If an event requires a diagnostic query, the DP slave answers in the next cycle with high
priority. The DP master queries the diagnostics, and continues with the cyclic data
communication.
The diagnostic telegram is divided into several parts. The 󹪝rst 6 bytes and their meanings are
bindingly speci󹪝ed in the standard. The obligatory 6 bytes are followed by optionally one or
several diagnostic blocks.
Three additional device-related diagnostic bytes are de󹪝ned for the PROFIBUS module. The 󹪝rst
device-related diagnostic byte de󹪝nes the header, and the next two de󹪝ne the number of
diagnostic bytes.
These diagnostic blocks have the format for the device-related diagnostics, and are not
speci󹪝ed any further in DP-V0. The meanings of the individual bits are speci󹪝ed in the GSD 󹪝le.
The following table shows the exact meanings of the bits for the SIDOOR ATD420W controller.
The diagnostic data relate exclusively to the internal communication bus between the SIDOOR
controller and the communication module.
Table 5-14 Device-related diagnostic bits
1.2 1.1 1.0 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 Device-related diagnostic bits
x Telegram length (LGE) false
x Remaining runtime exceeded
x Block check character (BCC) false
x Telegram start (STX) false
x Telegram type unknown (ADR)
x Slave address false
x Memory over󹪞ow
x Parity error
x Internal error
x Answer delay time exceeded
x Telegram type not identical
The 11 diagnostic bits are correspondingly divided between the two device-related diagnostic
bytes, i.e. bits 1.3 to 1.7 are not used or are reserved.
Controllers
5.5 Relay and 󹪝eldbus interfaces
ATD4xxW for industrial applications
148 System Manual, 06/2022, A5E51901827B AA