Commissioning
5.2 Basic commissioning
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
115
To change an existing address of a slave, the following procedure should be performed:
1.
Plug the AS-i Programmer into the addressing socket of the Inverter
2.
Turn the dial on the Programmer to the ADDR
posi-
tion. The display will indicate that this mo
de has
been selected.
3.
Press the
button; the screen will display
uSE
and the number of the lower addressed slave.
The existing slave addresses are shown at the b
ot-
tom of the display.
4.
Press the and buttons to select the slave address number to be changed.
5.
Press the
button; the display now shows
SEt
.
The selected number will begin to flash.
6.
Press the
and buttons to select the new
slave address number.
7.
Press the
button to confirm the new address.
ProG
is displayed briefly followed by confirmation of
the address change.