Alarms, faults and system messages
11.5 List of alarms and faults
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
301
Number
Cause
Remedy
A07991
Motor data identification activated
Switch on the motor and identify the motor data.
F08501 Setpoint timeout
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the set monitoring time p2044.
F08502 Monitoring time sign-of-life expired
Check the PROFINET connection.
F08510
Send configuration data not valid
Check the PROFINET configuration
A08511 Receive configuration data not
valid
A08526 No cyclic connection
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
A08565 Consistency error affecting adjust-
able parameters
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
F13100 Know-how protection: Copy protec-
tion error
The know-how protection and the copy protection for the memory card
are active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy protec-
tion cannot be activated
Insert a valid memory card.
F30001 Overcurrent Check the following:
Motor data, if required, carry out commissioning
Motor connection method (Υ / Δ)
U/f operation: Assignment of rated currents of motor and Power Mod-
ule
Line quality
Make sure that the line commutating reactor is connected properly
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
U/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit