Alarms, faults and system messages
11.5 List of alarms and faults
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
301
Motor data identification activated
Switch on the motor and identify the motor data.
F08501 Setpoint timeout
• Check the PROFINET connection.
• Set the controller to RUN mode.
• If the error occurs repeatedly, check the set monitoring time p2044.
F08502 Monitoring time sign-of-life expired
• Check the PROFINET connection.
Send configuration data not valid
• Check the PROFINET configuration
A08511 Receive configuration data not
A08526 No cyclic connection
• Activate the controller with cyclic operation.
• Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
A08565 Consistency error affecting adjust-
able parameters
Check the following:
• IP address, subnet mask or default gateway is not correct.
• IP address or station name used twice in the network.
• Station name contains invalid characters.
F13100 Know-how protection: Copy protec-
tion error
The know-how protection and the copy protection for the memory card
are active. An error occurred during checking of the memory card.
•
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
• Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy protec-
Insert a valid memory card.
F30001 Overcurrent Check the following:
• Motor data, if required, carry out commissioning
• Motor connection method (Υ / Δ)
• U/f operation: Assignment of rated currents of motor and Power Mod-
ule
• Line quality
• Make sure that the line commutating reactor is connected properly
• Power cable connections
• Power cables for short-circuit or ground fault
• Power cable length
• Line phases
If this doesn't help:
• U/f operation: Increase the acceleration ramp
• Reduce the load
• Replace the power unit