Alarms, faults and system messages
11.5 List of alarms and faults
SINAMICS G110M Operating Instructions
302 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
F30002 DC-link voltage overvoltage Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC link voltage controller (p1240, p1280).
Check the line voltage (p0210).
F30003 DC-link voltage undervoltage Check the line voltage (p0210).
F30004 Converter overtemperature Check whether the converter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
F30005 I2t converter overload Check the rated currents of the motor and Power Module.
Reduce current limit p0640.
When operating with U/f characteristic: Reduce p1341.
F30011 Line phase failure Check the converter's input fuses.
F30015 Motor cable phase failure Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
F30021 Ground fault
• Check the power cable connections.
• Check the motor.
• Check the current transformer.
• Check the cables and contacts of the brake connection (a wire might
be broken).
F30027 Time monitoring for DC link pre-
charging
Check the supply voltage at the input terminals.
Check the line voltage setting (p0210).
Overtemperature, intake air
• Check whether the fan is running.
• Check the fan filter elements.
• Check whether the ambient temperature is in the permissible range.
F30036 Overtemperature, inside area
F30037 Rectifier overtemperature See F30035 and, in addition:
• Check the motor load.
• Check the line phases
A30502 DC link overvoltage
• Check the unit supply voltage (p0210).
• Check the dimensioning of the line reactor.
Check that the sensor is connected correctly.
For further information, please refer to the List Manual.