3.5 Handheld programming unit
3-59
Siemens AG 2000 All Rights Reserved
SINUMERIK 840D Installation and Start-Up Guide (IAD) 04.00 Edition
3.5.3 Deviations from the standard HPU configuration
(up to SW 3.1)
The following documents are also required:
References: /BH/ Operator Components Manual
/FB/, P3, Basic PLC Program
/S7HT/ Manual, Application of Tools
The following features are examples of deviations from the standard configura-
tion:
S Changes to the address assignment
of the input, output or status bytes,
or flag area or data block
S Additional connection of an MCP
An example is given using the following configuration:
PLCCPU AS314
MCP
HPU
You must adjust the communication parameters and possibly the switch settings
(addresses) of the bus nodes.
To set a new configuration, first press the Define global data softkey. The fol-
lowing description of how to proceed is based on the assumption that you are
already familiar with this menu.
1. Set up a new project and CPU programs with the STEP7 tool. You must set
up a CPU program for each component of the system (PLC, MCP, HHU, 2nd
MCP, HPU...).
2. Network MPI nodes, i.e. network CPU programs with MPI address.
3. Call Global data menu (via File manager / MPI network / Options /
Global Data softkeys) and enter the desired configuration.
4. Compile this configuration. A new SDB is generated for each CPU program.
5. Set the cyclical transmit pattern. Once the configuration has been compiled
successfully for the first time, the Reduction ratio and Status can be acti-
vated and then input.
6. Compile your configuration again.
7. Transfer the SDB (from the CPU program of the PLC) to the PLC.
8. Call FB1, DB7 must be parameterized for all operator control components
(MPI nodes) in OB 100 in the basic PLC program.
9. The status pointer (double word) must be configured in FB1 for each compo-
nent for monitoring purposes.
Documentation
requirements
Example
Procedure
SIMATIC S7,
Version 2.1
3 Settin
g
s, MPI / OPI
08.97

Table of Contents

Other manuals for Siemens SINUMERIK 810D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK 810D and is the answer not in the manual?

Siemens SINUMERIK 810D Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK 810D
CategoryControl Unit
LanguageEnglish

Related product manuals