Detailed description
2.3 Feedrate control
Basic logic functions: Feeds (V1)
Function Manual, 11/2006, 6FC5397-0BP10-2BA0
51
Empty blocks
When chamfer or rounding is active, the possible number of blocks containing no traversing
information is limited.
The maximum number is defined in machine data:
MD20200 CHFRND_MAXNUM_DUMMY_BLOCKS.
The possible blocks without traversing information in the compensation plane are pure
dummy commands and are called empty blocks. For this reason, they may only be written
between two blocks with traversing information.
Constraints
Feedrate interpolation FLIN and FCUB is not possible for chamfer/rounding.
FRC/FRCM has no effect if a chamfer is being machined with G0; the command can be
programmed according to the F value without error message.
FRC is only effective if a chamfer/rounding is programmed in the same block or if RNDM
has been activated.
FRC overwrites the F or FRCM value for chamfer/rounding in the current block.
FRC/FRCM must be set to a value greater than zero.
FRCM=0 activates the feedrate programmed in F for the chamfer/rounding.
If FRCM is programmed, the FRCM value must be reprogrammed, equivalent to F, on a
G94G95 change, etc. If only F is reprogrammed and FRCM > 0 before the feedrate type
is changed, error message 10860 (no feedrate programmed) appears.

Table of Contents

Other manuals for Siemens SINUMERIK 810D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK 810D and is the answer not in the manual?

Siemens SINUMERIK 810D Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK 810D
CategoryControl Unit
LanguageEnglish

Related product manuals