EasyManuals Logo

Siemens SINUMERIK 810D Function Manual

Siemens SINUMERIK 810D
2184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #572 background imageLoading...
Page #572 background image
Detailed description
2.1 Mode group
Basic logic functions: Mode group, channel, program operation, reset response (K1)
14 Function Manual, 11/2006, 6FC5397-0BP10-2BA0
Channel gaps
Channels to which a mode group is assigned with machine data:
MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP
are regarded as activated.
Instead of a mode group number, the number "0" can be assigned to channels.
This has the following results:
The nonactivated channel does not take up memory space in the control.
Series machines with similar designs can be kept uniform during configuration. Only the
channels that can actually be used by the machine tool are activated (channels with
mode group number greater than 0).
Special case:
Channel 1 must always be available. If:
MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP [0] = 0
is specified, the following is automatically set by the control:
MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP [0] = 1 (BAG 1).
Example of configurations:
MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP[0] = 1
MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP[1] = 2
...
MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP[3] = 0 ; gap
...
MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP[8] = 1
MD10010 $MN_ASSIGN_CHAN_TO_MODE_GROUP[9] = 2

Table of Contents

Other manuals for Siemens SINUMERIK 810D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK 810D and is the answer not in the manual?

Siemens SINUMERIK 810D Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK 810D
CategoryControl Unit
LanguageEnglish

Related product manuals